cp

Products

Hien WKFXRS-15 II BM/A2 R32 Commercial Heat Pump Water Heater

Short Description:

Key Features:
The heat pump uses R32 eco-friendly refrigerant.
Higher water temperature output up to 60℃.
Full DC inverter heat pump.
With disinfection function.
Wi-Fi APP smart controlled.
Intelligent constant temperature.
High-quality material.
Operates down to ‑15℃.
Intelligent defrosting.
COP up to 5.0


Product Detail

Product Tags

Untitled

Key Features:
The heat pump uses R32 eco-friendly refrigerant.
Higher water temperature output up to 60℃.
Full DC inverter heat pump.
With disinfection function.
Wi-Fi APP smart controlled.
Intelligent constant temperature.
High-quality material.
Operates down to ‑15℃.
Intelligent defrosting.
COP up to 5.0

R32-Commercial-Heat-Pump-Water-Heater2

Powered by R32 green refrigerant, this heat pump delivers exceptional energy efficiency with a COP as high as 5.0.

This heat pump has a COP as high as 5.0. For every 1 unit of electrical energy consumed, it can absorb 4 units of heat from the environment, generating a total of 5 units of heat. Compared with traditional electric water heaters, it has a significant energy-saving effect and can greatly reduce electricity bills over the long term.

R32-Commercial-Heat-Pump-Water-Heater4

Maximum of 8 units can be controlled with one touch screen, delivering a combined capacity range from 15KW to 120KW.

Product Name Heat Pump Water Heater
Climate Type Ordinary
Model WKFXRS-15 II BM/A2 WKFXRS-32 II BM/A2
Power supply 380V 3N ~ 50HZ
Anti-electric Shock Rate Class l Class l
Test Condition Test Condition 1 Test Condition 2 Test Condition 1 Test Condition 2
Heating Capacity 15000W
(9000W~16800W)
12500W
(11000W~14300W)
32000W
(26520W~33700W)
27000W
(22000W~29000W)
Power input 3000W 3125W 6270W 6580W
COP 5.0 4.0 5.1 4.1
Working Current 5.4A 5.7A 11.2A 11.8A
Hot Water Yield 323L/h 230L/h 690L/h 505L/h
AHPF 4.4 4.38
Max Power Input/Max Running current 5000W/9.2A 10000W/17.9A
Max Outlet Water Temp 60℃ 60℃
Rated water flow 2.15m³/h 4.64m³/h
Water Pressure Drop 40kPa 40kPa
Max Pressure On High/LowPressure Side 4.5MPa/4.5MPa 4.5MPa/4.5MPa
Allowable Discharge/SucionPressure 4.5MPa/1.5MPa 4.5MPa/1.5MPa
Max Pressure On Evaporator 4.5MPa 4.5MPa
Water Pipe Connection DN32/1¼”internal thread DN40”internal thread
Sound Pressure  (1m) 56dB(A) 62dB(A)
Refrigerant/Charge R32/2. 3kg R32/3.4kg
Dimensions (LxWxH) 800×800×1075(mm) 1620×850×1200(mm)
Net Weight 131kg 240kg

 

Standard: GB/T 21362-2023
The nominal working condition 1 parameters of this technology are tested under working conditions: ambient dry bulb temperature 20℃, wet bulb temperature 15℃, initial water temperature 15℃, and end water temperature 55℃.
The nominal working condition 2 parameters were tested under ambient dry bulb temperature of 7℃, wet bulb temperature of 6℃, initial water temperature of 9℃, and final water temperature of 55℃.
The above parameters, if there are slight differences due to technical improvements, please refer to the relevant specifications of the actual product for accuracy.